MV Transformer — Primary Cable Sizing

Ampacity, voltage drop & short-circuit thermal withstand for medium-voltage transformer primary feeders — NEC 450 / IEEE C57 / ICEA basis
Dwg No.MV-001
ScaleNTS
MethodNEC 450 / ICEA P-32-382
Rev—
Reference tool only. Preliminary sizing aid for a medium-voltage transformer primary feeder. Cable ampacity, reactance and short-circuit withstand values used are representative/typical figures — verify against ICEA P-32-382 / P-54-440, the cable manufacturer's data, and NEC Article 450 before finalizing a design. Not a substitute for a qualified electrical engineer's design and a formal short-circuit/coordination study.
1
TransformerRating, primary voltage, impedance
▾
Sets the code reference cited for primary overcurrent protection sizing in the results and report. CSA C22.1 governs by default; switch to NEC only where the project is under U.S. jurisdiction.
2.4 kV
4.16 kV
12.47 kV
13.2 kV
13.8 kV
24.94 kV
34.5 kV
Typical %Z rises with rating — roughly 2–5% for smaller units, 5.5–7%+ for larger distribution-class units. Use the nameplate value once a unit is selected.
2
Primary CableLength, material, insulation class, sets
▾
Insulation voltage class should be rated for the system voltage (100% or 133% insulation level per the cable manufacturer's recommendation for the grounding configuration in use).
3
Upstream Short-CircuitAvailable fault current at the primary terminals
▾
Default 90°C/250°C matches typical 90°C-rated EPR/XLPE shielded MV cable — confirm the exact short-circuit temperature limit against the cable manufacturer's data for the insulation actually selected.
4
Primary Protection (optional)Clearing time at the fault current above, if known
If you know the primary fuse/breaker's actual clearing time at the fault current entered in Step 3, enter it here to check the cable's short-circuit withstand against it. If left off, the tool instead reports how long the selected cable can withstand that fault current before reaching its thermal damage limit.

Result — Recommended Primary Cable

—
Recommended size
Transformer FLA (primary)
—
Required ampacity (125% FLA)
—
Cable ampacity (this size)
—
Voltage drop, this length
—
Short-circuit withstand time
—
Max primary fuse
—
Max primary breaker
—

Report Pages

save each transformer/cable run, then compile them into one document
Saved pages are stored in this browser only (not uploaded anywhere). Compiling renumbers pages automatically based on the order and selection below.

Calculation Ledger

FLA → ampacity → voltage drop → thermal withstand

All Sizes Evaluated

SizeAmpacityVD%Withstand (s)Meets all?